The switch, the patch panel, the NAS and the mini PC all bolt to the same two columns of holes. Two dimensions govern any panel you print: 1U is 44.45 mm (1.75″) tall, and the hole columns sit 465.1 mm apart. Space the holes evenly and the top one in every U lands 2 mm low and will not go in, even in the first U; draw the panel 44.45 tall and it rubs on its neighbors.
The rack unit and its holes
The 19″ rack is defined by EIA-310 (revision E, also published as CEA-310-E in 2005) and IEC 60297-3-100. The 535 mm ETSI metric rack is a separate, less common system and is not covered here. Both standards are paywalled; these values are the ones quoted by Wikipedia and by a rack maker's FAQ, checked against each other.
The trap is in the holes: each U has three per post, but they are not evenly spaced. They sit 6.35, 22.225 and 38.1 mm above the bottom of the U, so the gaps are 15.875, 15.875 and 12.7 mm (5/8″, 5/8″, 1/2″). The close pair, 12.7 apart, straddles the boundary between two Us: on a rack with unnumbered posts, that is how you find where each U starts.
A panel is 0.79 mm (1/32″) shorter than the sum of its Us, half at the top and half at the bottom, so it slides in and out without rubbing on the panels either side. That is why, measured from the panel's bottom edge, its hole positions are 0.397 mm lower than in the U.
| U | Panel height (44.45·n − 0.79) | Holes from the panel's bottom edge |
|---|---|---|
| 1U | 43.66 | 5.95 · 21.83 · 37.70 |
| 2U | 88.11 | the 1U ones plus 50.40 · 66.28 · 82.15 |
| 3U | 132.56 | + 44.45 per U |
| 4U | 177.01 | + 44.45 per U |
Source: en.wikipedia.org/wiki/19-inch_rack and the RackSolutions FAQ; panel heights and hole positions calculated.
Most panels use only the two outer holes of each U (5.95 and 37.70, 31.75 apart); the middle one is optional. The classic drawing mistake is spacing all three holes at 44.45/3 = 14.82. Because three of those steps add up to exactly 44.45, the series lines up with the first hole of every U and misses the other two, the same in every U: the middle one is 1.06 mm low and the top one 2.12. The panel's horizontal slots (see "Screws, cage nuts and holes") absorb no vertical error. Copy the three positions. What does accumulate is rounding the U pitch to 44 or 45 mm: half a millimeter per U, about 2 mm over a 4U panel.
Widths: 19 and 10 inches
| Dimension | 19″ (EIA-310) | 10″ (mini rack) |
|---|---|---|
| Panel width with ears | 482.6 | 254 |
| Between hole columns | 465.1 (18.312″; the standard allows 464.3–465.8) | 236.525 (9.312″, manufacturers' convention) |
| Opening between posts | ≥ 450 (typically 450.85 = 17.75″) | no standard: equipment ≤ 210 wide, ≈ 220 at most |
| Hole center from the panel end | 8.75 | 8.74 |
| Ear width (end to opening) | 15.875 | ≈ 16–17 (depends on the opening; measure it) |
Source: en.wikipedia.org/wiki/19-inch_rack; for 10″, the Project Mini Rack README (github.com/geerlingguy/mini-rack).
The 10″ rack has no formal standard. The U and the vertical pattern are the 19″ ones; the horizontal spacing is a convention that some makers stray from by a millimeter. That is why printed panels get horizontal slots (next section), and why you should measure your rack before you draw (Measuring an undocumented standard). The opening between posts is not fixed either: Wikipedia gives 222.25, but Project Mini Rack recommends keeping equipment under about 210 mm wide. There are commercial 10″ racks (DeskPi RackMate) and printable ones (those the README lists), but none of them is a standard.
Depth is not standardized: four-post cabinets usually come in 600, 800 or 1000 mm; wall-mount and 10″ racks are a good deal shallower. Measure your rack's usable depth before you design a shelf.
A printed ear is an L: the flange screws to the post and the leg runs along the side of the equipment. The legs take up room in the opening. The equipment that fits between them is the panel width minus twice what each ear protrudes: with 25 mm a side, 482.6 − 2 · 25 = 432.6 on 19″ and 254 − 50 = 204 on 10″, inside the recommended 210.
Screws, cage nuts and holes
Posts come in two kinds. Square-hole posts, 9.5 mm (0.375″) for cage nuts, are the norm in server cabinets everywhere: M6 in Europe, 10-32 or 12-24 in the US. Tapped posts, in 10-32 UNF, 12-24 or M6, are typical of two-post telecoms and AV racks, and of many 10″ ones. A cage nut clips into steel sheet roughly 1 to 4 mm thick; the exact range depends on the nut, so check its datasheet. In a thicker printed post it will not grip: use heat-set inserts or captive nuts there (Designing for heat-set inserts, Captive nuts and clearance holes). A fully printed rack, with its own 15 mm grid that does not follow the EIA pitch, is covered in HomeRacker: modular printed racks.
EIA-310 dimensions the rack, not the panel: panel holes are not in it. Use the ISO 273 medium-series clearance hole plus your hole compensation, as a horizontal slot: for M6, 6.6 + 2 × 0.05 = 6.7 wide; for M5 or 10-32 (4.83 major diameter), 5.5 + 0.1 = 5.6. A 12-24 is 5.49 across: in a 5.6 slot it either jams or will not go in at all, so use the M6 slot. Why holes print small explains why the compensation is needed; Metric fasteners has the clearance-hole table.
Make the slot its width plus 4 mm of travel long (10.7 for M6). That takes up the 464.3 to 465.8 tolerance and the spread between 10″ racks. Check it stays on the ear: 8.75 + (4 + 6.7)/2 = 14.1, less than 15.875. A longer slot runs into the opening behind the post.
Put a flat washer under the screw head on a printed ear. On plastic, the clamp load relaxes through creep and the screw works loose within a few months (Creep and fatigue).
Worked example: a 1U 19″ panel on a 256 bed
The job: a 1U blank panel with six keystone openings for a patching area, in PETG. As of late 2026, plenty of desktop printers have 250–256 mm beds; this one is 256 × 256.
Height 43.66; thickness 4 mm. Commercial steel panels are 1.5–3 mm, but a printed one needs more stiffness. Holes: two per side at 5.95 and 37.70 from the bottom edge, centered 8.75 from each end, in 6.7 × 10.7 slots for M6.
The 482.6 panel does not fit on 256, not even diagonally: along the 362 mm diagonal, a strip 43.66 wide can be at most √2 · 256 − 43.66 ≈ 318 mm long. Split the panel down the middle into two 241.3 halves, which fit both 256 and 250 beds. Run the cut between two keystone openings, where there is more material, never through one. Join the halves with a backing strip screwed or glued behind the joint, or with a dovetail; the rules for the cut, the dowels and the clearances are in Splitting large parts and Printed dovetails and joinery.
Print each half face down on the bed: the visible face comes out smooth, and the holes and keystone openings print with their axes vertical, with no ceilings to bridge. The 14.9 × 19.2 keystone cutout is meant for a 1.5–1.6 mm panel, so on a 4 mm one, pocket the back face around each opening so the latch can catch (Keystone jacks and wall plates).
On 10″ the problem goes away: a 254 × 43.66 1U panel fits whole on a 256 bed, which is why the mini rack is the format that suits printing best. On a 250 × 220 bed, rotate it about 25° and it fits. On a 180 × 180 bed it does not fit even diagonally, and has to be split too.
Ears and shelves: what carries the weight
A front panel carries only its own weight. Equipment hung only from its front ears loads them with its weight plus a moment. With 2 kg of equipment and its center of mass 100 mm behind the flange: M = 2 × 9.81 × 0.100 = 1.96 N·m, about 0.98 N·m and 9.8 N per ear.
The leg running along the side of the equipment, 3 mm thick and 43.66 tall, bends edgewise: σ = 6M/(t·h²) = 6 × 981 / (3 × 43.66²) ≈ 1.0 MPa (M = 981 N·mm, t = leg thickness, h = its height), negligible.
The flange is another matter. It carries the moment to the two screws, 31.75 apart, as a couple: F ≈ 0.98 / 0.03175 ≈ 31 N, the top one pulling and the bottom one bearing on the post. That force acts 25 − 8.75 = 16.25 mm from the leg, so at the root of the flange M ≈ 31 × 16.25 ≈ 500 N·mm. With an effective width of about 22 mm and 4 mm thickness, σ = 6 × 500 / (22 × 4²) ≈ 8.5 MPa, eight times the stress in the leg, and it grows in proportion to how far the ear protrudes. The flange root is what you need to protect; to run the numbers for your own equipment, see Estimating whether a part will hold.
How strong that root is depends on orientation: anything that bends prints with its length in the layer plane (Layer orientation for mechanisms). Print the ear with the outline of the L flat on the bed (the ear's height along Z): the beads wrap round the corner. With the leg lying flat on the bed, the flange grows in layers and splits along one of them at the root (Layer adhesion and anisotropy). Add a gusset in the corner and a root fillet of r ≈ 0.5 t (Ribs, gussets and fillets). Printed this way, the flange slots are horizontal holes 6.7 tall: above 6 mm the ceiling sags 0.1–0.3 mm, which a slot tolerates without a teardrop.
A panel or an ear in the exhaust of a switch or a NAS can go above 40 °C; check with a thermometer at the outlet. Under load, PLA works up to about 40 °C, PETG up to 50 and ASA up to 80–85 (Heat, cold, sunlight and chemicals). For sustained load next to hot equipment use PC, ASA or a fiber-filled grade; PLA and PETG are fine for a light load with no heat (Creep and fatigue).
A rule of thumb: if the metal version of your equipment comes with rear brackets or rails, the printed one needs rear support too. Deep or heavy equipment goes on a shelf: in a four-post rack, bolted front and back; in a two-post rack, cantilevered from the front with a gusset underneath. A 10″ shelf (254 wide) fits whole on a 256 bed; for 19″, buy a steel shelf and print the trays or holders that sit on it.
When it fails
| Symptom | Cause | Fix |
|---|---|---|
| The panel rubs or will not fit between its neighbors | Drawn 44.45·n tall | 44.45·n − 0.79 (43.66 for 1U) |
| The top hole in every U will not go in, starting with the first U | Evenly spaced holes (14.82) | 6.35 / 22.225 / 38.1 from the bottom of the U |
| Each U is further off than the one before | Rounded U pitch (44 or 45) | Exactly 44.45 |
| Nothing lines up vertically | Panel positioned from the wrong hole | The U boundary is at the pair 12.7 apart |
| One side fits and on the other the holes are a millimeter out | 464.3–465.8 tolerance, or a 10″ rack with its own convention | Horizontal slots with 4 mm of travel |
| The equipment will not pass between the posts | Equipment plus ear legs is wider than the opening (450 / ≈ 210–220) | Thinner legs or ears that protrude further |
| The ear cracks along a layer at the flange root | Printed with the leg lying flat | Outline of the L flat on the bed, with a gusset |
| After a few weeks the equipment tips forward and the ears bend | Heavy or deep equipment hung only at the front; PLA in hot air | Rear support or a shelf; PC, ASA or a fiber-filled material |
| The screw works loose over the months | Clamp load relaxes with the head on plastic | Washer; inserts in a printed post |
| The cage nut will not clip into a printed post | Post thicker than the nut's sheet range | Heat-set insert or captive nut |
| The two halves of a split panel leave a step | Joint not located | Dowels, a chamfer and clamping while the adhesive cures (Splitting large parts) |
How to test it
Before the full print, print a 20 mm wide strip from one end of the panel, at its real height and with its slots: it takes ten minutes. If the panel is 2U or more, so is the strip, because a rounded U pitch only shows from the second U onwards. Hold it against the post: every screw has to go in without forcing (Test coupons).
With ears that carry equipment, leave it hanging for 48 hours and measure with a rule how far its back edge drops (Testing a mechanism before you trust it).